UPSMON(8)	     Network UPS Tools (NUT)		UPSMON(8)

NAME
       upsmon - UPS monitor and shutdown controller

SYNOPSIS
       upsmon -h

       upsmon -c command

       upsmon [-d] [-i] [-p] [-u user]

DESCRIPTION
       upsmon  is  the client process that is responsible for the
       most important part of UPS monitoring - shutting down  the
       system  when the power goes out.	 It can call out to other
       helper programs for  notification  purposes  during  power
       events.

       upsmon  can  monitor  multiple systems using a single pro-
       cess.  Every UPS that is	 defined  in  the  upsmon.conf(5)
       configuration  file  is	assigned a power value and a type
       (slave or master).

OPTIONS
       -h     Display the help message.

       -c command
	      Send the command command	to  the	 existing  upsmon
	      process.	Valid commands are:

	      fsd - shutdown all master UPSes (use with caution)

	      stop - stop monitoring and exit

	      reload  - reread upsmon.conf(5) configuration file.
	      See "reloading nuances" below if this doesn't work.

       -d     Enable  debugging	 mode.	 upsmon runs in the fore-
	      ground and prints debugging information  on  stdout
	      about the monitoring process.

       -i     Enable infinite loop at shutdown.	 upsmon will keep
	      a process running after calling the  shutdown  com-
	      mand  rather  than exiting.  This is only useful if
	      you have shutdown scripts that complain when upsmon
	      isn't running as they kill various processes.

       -p     Run  privileged all the time.  Normally upsmon will
	      split into two processes.	 The majority of the code
	      runs  as an unprivileged user, and only a tiny stub
	      runs as root.  This switch will disable that  mode,
	      and run the old "all root all the time" system.

       -u user
	      Set  the	user for the unprivileged monitoring pro-
	      cess.  This has no effect when using -p.

	      The default user is  set	at  configure  time  with
	      'configure  --with-user=...'.   Typically	 this  is
	      'nobody', but  other  distributions  will	 probably
	      have  a specific 'nut' user for this task.  If your
	      notification scripts need	 to  run  as  a	 specific
	      user, set it here.

	      You  can	also  set this in the upsmon.conf(5) file
	      with the RUN_AS_USER directive.

UPS DEFINITIONS
       In the upsmon.conf(5), you must specify at least	 one  UPS
       that will be monitored.	Use the MONITOR directive.

	    MONITOR system powervalue username password type

       The  system  refers  to	a  upsd(8)  server,  in	 the form
       [<upsname>@]hostname[:port].  The simplest form is just	a
       hostname, i.e.:

	    "localhost" refers to the first UPS on the local sys-
       tem.

       Other possibilities include:

	    "su700@mybox" means a UPS called "su700" on a  system
       called "mybox".

	    "elvis:1234"  means	 the first UPS on a system called
       "elvis", port 1234.

       Finally, to use all of these options:

	    "fenton@bigbox:5678" is a UPS called  "fenton"  on	a
       system  called "bigbox" which runs upsd(8) on port "5678".
       Phew!

       The powervalue refers to how many power supplies	 on  this
       system  are  being driven this UPS.  This is typically set
       to 1, but see the section on power values below.

       The username is a  section  in  your  upsd.users(5)  file.
       Whatever	 password  you set in that section must match the
       password set in this file.

       The type set in that section must also match the type here
       -  master  or  slave.  In general, a master process is one
       running on the system with the UPS actually plugged into a
       serial port, and a slave is drawing power from the UPS but
       can't talk to it directly.  See the section on  UPS  types
       for more.

NOTIFY EVENTS
       upsmon  senses  several	events	as  it monitors each UPS.
       They are called notify events as they can be used to  tell
       the  users and admins about the change in status.  See the
       additional NOTIFY-related sections below	 for  information
       on customizing the delivery of these messages.

       ONLINE The UPS is back on line.

       ONBATT The UPS is on battery.

       LOWBATT
	      The  UPS	battery	 is  low  (as  determined  by the
	      driver).

       FSD    The UPS has been commanded into the  "forced  shut-
	      down" mode.

       COMMOK Communication with the UPS has been established.

       COMMBAD
	      Communication with the UPS was just lost.

       SHUTDOWN
	      The local system is being shut down.

       REPLBATT
	      The UPS needs to have its battery replaced.

       NOCOMM The UPS can't be contacted for monitoring.

NOTIFY COMMAND
       In  upsmon.conf(5), you can configure a program called the
       NOTIFYCMD that will handle events that occur.

	    NOTIFYCMD "path to program"

	    NOTIFYCMD "/usr/local/bin/notifyme"

       Remember to wrap the path in "quotes" if it  contains  any
       spaces.

       The program you run as your NOTIFYCMD can use the environ-
       ment variables NOTIFYTYPE and UPSNAME  to  know	what  has
       happened and on which UPS.  It also receives the notifica-
       tion message (see below) as the first (and only) argument,
       so you can deliver a preformatted message too.

       Note  that  the	NOTIFYCMD will only be called for a given
       event when you set the  EXEC  flag  by  using  the  notify
       flags, below:

NOTIFY FLAGS
       By  default,  all  notify  events  (see	above) generate a
       global message (wall) to all users, plus they  are  logged
       via  the	 syslog.  You can change this with the NOTIFYFLAG
       directive in the configuration file:

	    NOTIFYFLAG notifytype flags

	    Examples:

	    NOTIFYFLAG ONLINE SYSLOG

	    NOTIFYFLAG ONBATT SYSLOG+WALL

	    NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC

       The flags that can be set on a given notify event are:

       SYSLOG Write this message to the syslog.

       WALL   Send this message to all users on	 the  system  via
	      'wall'.

       EXEC   Execute the NOTIFYCMD.

       IGNORE Don't  do anything.  If you use this, don't use any
	      of the other flags.

       You can mix  these  flags.   "SYSLOG+WALL+EXEC"	does  all
       three for a given event.

NOTIFY MESSAGES
       upsmon  comes with default messages for each of the NOTIFY
       events.	These can be changed with  the	NOTIFYMSG  direc-
       tive.

	    NOTIFYMSG type "message"

	    Examples:

	    NOTIFYMSG ONLINE "UPS %s is getting line power"

	    NOTIFYMSG ONBATT "Someone pulled the plug on %s"

       The  first  instance of %s is replaced with the identifier
       of the UPS that generated the event.  These  messages  are
       used when sending walls to the users directly from upsmon,
       and are also passed to the NOTIFYCMD.

POWER VALUES
       The "current overall power value" is the sum of all  UPSes
       that  are  currently  able  to  supply power to the system
       hosting upsmon.	Any UPS that is either on line or just on
       battery	contributes to this number.  If a UPS is critical
       (on battery and low battery) or has been put into  "forced
       shutdown" mode, it no longer contributes.

       A  "power  value"  on a MONITOR line in the config file is
       the number of power supplies that the UPS runs on the cur-
       rent system.

	    MONITOR upsname powervalue username password type

       Normally,  you  only  have one power supply, so it will be
       set to 1.

	    MONITOR myups@myhost 1 username mypassword master

       On a large server with redundant power supplies, the power
       value  for a UPS may be greater than 1.	You may also have
       more than one of them defined.

	    MONITOR ups-alpha@myhost 2 username mypassword master

	    MONITOR ups-beta@myhost 2 username mypassword master

       You can also set the power value for a UPS to 0 if it does
       not supply any power to that system.   This  is	generally
       used when you want to use the upsmon notification features
       for a UPS even though it's not actually running the system
       that  hosts upsmon.  Don't set this to "master" unless you
       really want to power this UPS off when  this  instance  of
       upsmon needs to shut down for its own reasons.

	    MONITOR   faraway@anotherbox  0  username  mypassword
       slave

       The "minimum power value" is the number of power	 supplies
       that must be receiving power in order to keep the computer
       running.

	    MINSUPPLIES value

       Typical PCs only have 1, so most users will leave this  at
       the default.

	    MINSUPPLIES 1

       If  you	have  a	 server	 or similar system with redundant
       power, then this value will usually be  set  higher.   One
       that  requires  three  power supplies to be running at all
       times would simply set it to 3.

	    MINSUPPLIES 3

       When the current overall power value drops below the mini-
       mum  power  value,  upsmon  starts  the shutdown sequence.
       This design allows you to lose some of your power supplies
       in a redundant power environment without bringing down the
       entire system while still  working  properly  for  smaller
       systems.

UPS TYPES
       upsmon  and  upsd(8)  don't always run on the same system.
       When they do, any UPSes that are directly attached to  the
       upsmon  host  should  be monitored in "master" mode.  This
       makes upsmon take charge of that equipment,  and	 it  will
       wait  for  slaves  to  disconnect before shutting down the
       local system.  This allows the distant systems (monitoring
       over  the  network)  to shut down cleanly before upsdrvctl
       shutdown runs and turns them all off.

       When upsmon runs as a slave, it is relying on the  distant
       system  to  tell it about the state of the UPS.	When that
       UPS goes critical (on battery and low battery), it immedi-
       ately  invokes  the local shutdown command.  This needs to
       happen quickly.	Once  it  disconnects  from  the  distant
       upsd(8) server, the master upsmon will start its own shut-
       down process.  Your slaves must all shut down  before  the
       master  turns  off  the	power  or  filesystem  damage may
       result.

       upsmon deals with slaves that get wedged, hang, or  other-
       wise  fail  to  disconnect from upsd(8) in a timely manner
       with the HOSTSYNC timer.	 During a shutdown situation, the
       master upsmon will give up after this interval and it will
       shut down anyway.  This	keeps  the  master  from  sitting
       there  forever (which would endanger that host) if a slave
       should break somehow.  This defaults to 15 seconds.

       If your master system is shutting down  too  quickly,  set
       the  FINALDELAY	interval  to  something	 greater than the
       default 15 seconds.  Don't set this too high, or your  UPS
       battery may run out of power before the master upsmon pro-
       cess shuts down that system.

TIMED SHUTDOWNS
       For those rare situations where the shutdown process can't
       be  completed  between  the  time that low battery is sig-
       nalled and the UPS actually powers off the load,	 use  the
       upssched(8)  helper  program.   You  can use it along with
       upsmon to schedule a shutdown based on  the  "on	 battery"
       event.	upssched can then come back to upsmon to initiate
       the shutdown once it's run on battery too long.

       This can be complicated and messy, so stick to the default
       critical UPS handling if you can.

REDUNDANT POWER SUPPLIES
       If  you	have  more  than  one  power supply for redundant
       power, you may also have more than one  UPS  feeding  your
       computer.  upsmon can handle this.  Be sure to set the UPS
       power values appropriately and the MINSUPPLIES value  high
       enough  so that it keeps running until it really does need
       to shut down.

       For example, the HP NetServer LH4 by default has	 3  power
       supplies	 installed, with one bay empty.	 It has two power
       cords, one per side of the box.	This means that one power
       cord  powers  two power supply bays, and that you can only
       have two UPSes supplying power.

       Connect UPS "alpha" to the cord	feeding	 two  power  sup-
       plies, and UPS "beta" to the cord that feeds the third and
       the empty slot.	Define alpha as a powervalue  of  2,  and
       beta as a powervalue of 1.  Set the MINSUPPLIES to 2.

       When  alpha  goes  on  battery, your current overall power
       value will stay at 3, as it's still supplying power.  How-
       ever,  once it goes critical (on battery and low battery),
       it will stop contributing to  the  current  overall  power
       value.  That means the value will be 1 (beta alone), which
       is less than 2.	That is insufficient to run  the  system,
       and upsmon will invoke the shutdown sequence.

       However,	 if beta goes critical, subtracting its contribu-
       tion will take the current overall  value  from	3  to  2.
       This  is	 just  high enough to satisfy the minimum, so the
       system will continue running as before.	If  beta  returns
       later,  it  will be re-added and the current value will go
       back to 3.  This allows you to swap out	UPSes,	change	a
       power  configuration, or whatever, as long as you maintain
       the minimum power value at all times.

MIXED OPERATIONS
       Besides being able to monitor multiple UPSes,  upsmon  can
       also  monitor them as different roles.  If you have a sys-
       tem with multiple power supplies serviced by separate  UPS
       batteries, it's possible to be a master on one and a slave
       on the other.  This usually happens when you  run  out  of
       serial ports and need to do the monitoring through another
       system nearby.

       This is also complicated, especially when it comes time to
       power down a UPS that has gone critical but doesn't supply
       the local system.  You can do  this  with  some	scripting
       magic  in  your notify command script, but it's beyond the
       scope of this manual.

FORCED SHUTDOWNS
       When upsmon is forced to bring down the local  system,  it
       sets the "FSD" (forced shutdown) flag on any UPSes that it
       is running in master mode.  This is  used  to  synchronize
       slaves in the event that a master UPS that is otherwise OK
       needs to be brought down due to some pressing event on the
       master.

       You  can manually invoke this mode on the master upsmon by
       starting another copy with '-c fsd'.  This is useful  when
       you  want to initiate a shutdown before the critical stage
       through some external means, such as upssched(8).

DEAD UPSES
       In the event that upsmon can't reach upsd(8), it	 declares
       that UPS "dead" after some interval controlled by DEADTIME
       in the upsmon.conf(5).  If this happens while that UPS was
       last  known  to	be on battery, it is assumed to have gone
       critical and no longer contributes to  the  overall  power
       value.

       upsmon will alert you to a UPS that can't be contacted for
       monitoring with a "NOCOMM" notifier by default  every  300
       seconds.	 This can be changed with the NOCOMMWARNTIME set-
       ting.

RELOADING NUANCES
       upsmon usually gives up root powers for the  process  that
       does  most  of  the  work, including handling signals like
       SIGHUP to reload the configuration file.	 This means  your
       upsmon.conf(8)  file  must  be  readable	 by  the non-root
       account that upsmon switches to.

       If you want reloads to work, upsmon must run as some  user
       that  has  permissions  to read the configuration file.	I
       recommend making a new user just for this purpose, as mak-
       ing the file readable by "nobody" (the default user) would
       be a bad idea.

       See the RUN_AS_USER section in upsmon.conf(8) for more  on
       this topic.

       Additionally,  you  can't change the SHUTDOWNCMD or POWER-
       DOWNFLAG definitions with a reload due to  the  split-pro-
       cess  model.   If  you  change those values, you must stop
       upsmon and start it back up.  upsmon will warn you in  the
       syslog  if you make changes to either of those values dur-
       ing a reload.

SIMULATING POWER FAILURES
       To test a synchronized shutdown without pulling	the  plug
       on  your	 UPS(es),  you	need only set the forced shutdown
       (FSD) flag on them.  You can do	this  by  calling  upsmon
       again to set the flag - i.e.:

	    upsmon -c fsd

       After  that, the master and the slaves will do their usual
       shutdown sequence as if the  battery  had  gone	critical.
       This  is	 much  easier on your UPS equipment, and it beats
       crawling under a desk to find the plug.

FILES
       upsmon.conf(5)

SEE ALSO
   Server:
       upsd(8)

   Clients:
       upsc(8), upscmd(8), upsrw(8), upsmon(8)

   CGI programs:
       upsset.cgi(8), upsstats.cgi(8), upsimage.cgi(8)

   Internet resources:
       The    NUT    (Network	 UPS	Tools)	   home	    page:
       http://www.exploits.org/nut/

       NUT     mailing	  list	  archives    and    information:
       http://lists.exploits.org/

			 Tue Oct 15 2002		UPSMON(8)
[top]

List of man pages available for IRIX

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net