UPSCMD(8)	     Network UPS Tools (NUT)		UPSCMD(8)

NAME
       upscmd - UPS administration program for instant commands

SYNOPSIS
       upscmd -h

       upscmd -l ups

       upscmd [-u username] [-p password] ups command

DESCRIPTION
       upscmd allows you to invoke "instant commands" in your UPS
       hardware.  Not all hardware supports this,  so  check  the
       list  with  -l to see if anything will work on your equip-
       ment.

       On hardware that supports it, you can use this program  to
       start  and  stop	 battery tests, invoke a front panel test
       (beep!), turn the load on or off, and more.

OPTIONS
       -h     Display the help message.

       -l ups Show the list of supported instant commands on that
	      UPS.  Some hardware may not support any of them.

       -u username
	      Set  the username for the connection to the server.
	      This is optional, and you will be prompted for this
	      when invoking a command if -u is not used.

       -p password
	      Set  the	password  to  authenticate to the server.
	      This is also optional like  -u,  and  you	 will  be
	      prompted for it if necessary.

       ups    Connect to that UPS.  The format for this option is
	      [upsname@]hostname[:port].

UNATTENDED MODE
       If you run this program inside a shell script  or  similar
       to  invoke  a command, you will need to specify all of the
       information on the command line.	 This means using -u  and
       -p.   Otherwise	it  will put up a prompt and your program
       will hang.

       This is not necessary when displaying  the  list,  as  the
       username and password are not required for read-only mode.

DANGEROUS COMMANDS
       Some drivers like apcsmart(8) have built-in  paranoia  for
       the  dangerous  commands	 like OFF.  To make them actually
       turn off the load, you will have to send the command twice
       within  a short window.	That is, you will have to send it
       once, then send it again after 3 seconds elapse but before
       15 seconds pass.

       This paranoia is entirely defined within the driver.  upsd
       and upscmd have no control over the timing.

DIAGNOSTICS
       upscmd won't work unless you provide a valid username  and
       password.   If  you  get "access denied" errors, make sure
       that your upsd.users(5) has an entry for you, and that the
       username you are using has permissions to SET variables.

BUGS
       There is currently no way to tell the user when the driver
       requires confirmation to invoke a  command  such	 as  OFF.
       Similarly,  there  is  not yet a way to tell the user if a
       command succeeds or fails.

SEE ALSO
       upsd(8), upsrw(8)

   Internet resources:
       The    NUT    (Network	 UPS	Tools)	   home	    page:
       http://www.exploits.org/nut/

       NUT     mailing	  list	  archives    and    information:
       http://lists.exploits.org/

			 Sun Aug 31 2002		UPSCMD(8)
[top]

List of man pages available for IRIX

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net